SJG-2083 Industrial Acid Concentration Meter
SJG-2083 Industrial Acid Concentration Meter is our company’s latest micro-computer based high-end instrument. All the information in the instrument is displayed in English. It is characterized by complete English display, English menu operation, intelligence, multiple functions, high measuring performance, and strong environment adaptability. It can be widely used in thermal power plants, chemical industry and other industries. It can be used to test the concentration of the regenerated liquid in high-purity water preparation process by means of ion exchange. It can also be used for continuously monitoring the concentration of the hydrochloric acid in the pickling solutions for clean boilers and pipelines.
Features :
Intelligent: SJG-2083 English On-line Acid Concentration Meter adopts high-precision AD conversion and |
single chip microcomputer processing technologies. It can be used for the measurement of the HCL |
concentration and temperature, automatic temperature compensation, automatic range switching and |
self-checking. |
Reliability: All the components are arranged on one circuit board. No complicated functional switch, adjusting |
knob or potentiometer is arranged on this instrument. |
Strong interference immunity: Its current output adopts optoelectronic isolating technology. This meter has |
strong interference immunity and the capacity of long-distance transmission as well as excellent electromagnetic |
compatibility. |
Waterproof and dust-proof design: Its protection grade is IP65. It is applicable for outdoor use. |
Automatic range switching: The measuring ranges can automatically switch within the measuring range of the |
electrode. |
Communication interface: It can be easily connected to a computer to perform monitoring and communication. |
Phase sensitive detection: Eliminating the influence of conductors on the measurement of hydrochloric acid |
concentration. |
Automatic measuring frequency switching: This can help prevent electrodes from polarization, so as to enhance |
their accuracy. |
Technical Indexes :
1. Measuring range: concentration: (0~10)% HCL; (0~30)% HCL; temperature: 0~99.9°C |
2. Intrinsic error of electronic units: concentration: ±1.0%; temperature: ±0.3°C |
3. Range of automatic temperature compensation: 0~99.9°C |
4. Solution tested: 0~99.9°C, 0.6MPa |
5. Intrinsic error of the instrument: concentration: ±2.0% (the error may be less than 0.05% after usual point |
calibration.) |
Temperature: ±0.5°C(0.0°C≤T≤80.0°C) |
6. Repeatability error of the electronic unit: ±1.0% |
7. Stability of the electronic unit: ±1.0%/24h |
8. Isolated current output: 4~20 mA(load <750Ω) |
9. Output current error: ≤±1%FS |
10. Compensation range of the temperature coefficient: (0-10.0)% /°C (adjustable) |
11. Alarm relay: AC 220V, 3A |
12. Communication interface: RS485 or 232(optional) |
13. Power supply: AC220V±22V, 50Hz±1HZ |
14. Protection grade: IP65 |
15. Clock accuracy: ±1 minute/month |
16. Data storage capacity: l month (1 point/5 minutes) |
17. Saving time of data under a continuous power-failure condition: 10 years |
18. Overall dimension: 146 (length) x 146 (width) x 108 (depth) mm; dimension of the hole: 138 x 138mm |
19. Working conditions: ambient temperature: 0-60°C; relative humidity <85% |
20. Weight: 1.0kg |