Hot Selling type LC1-D contactor
1.Rated voltage:110~660V
2.Rated current:9~150A
3.Poles:3/4P
4.Auxiliary of contact:1NO+1NC/2NO+2NC
5.Standard:IEC60947-2
CONNECTIONS FOR POWER AND CONTROL CIRCUITS:
Type of contactor | | | CYC1-D09...D18 DT20& DT25 | CYC1-D25...D38 DT32 & DT40 | CYC1-D40 | CYC1-D050...D95 | CYC1-D115& DT25CYC1-D150 |
ENVIRONMENT
Rated insulation voltage(Ui) | Conforming to IEC 947-4-1, over voltage category III, degree fo pollution:3 | V | 690 | 690 | 1000 | 1000 | 1000 |
Rated impulse with stand voltage(Uimp) | Conforming to IEC 947 | KV | 6 | 6 | 8 | 8 | 8 |
Conforming to standards | | | IEC 947-1,947-4-1,EN60947-1,EN60947-4-1 |
Degree of protection(1) | Power connection | | Protection against direct finger contact IP2X |
(front face only) | Coil connection | | Protection against direct finger contact IP2X (except CYC1-D40...D80) |
protective treatment | Conforming to IEC 68 | | "TH" |
Ambient air temperature | Storage | °C | -60...+80 |
around the device | operation | °C | -5...+60 |
| Permissible | °C | -40...+70,for operation at Uc |
Maximum operating altitude | Without derating | m | 3000 |
Operating position | Without derating | | ±30°possible,in relation to normal vertical mounting plant |
Flame resistance | Conforming to IEC 695-2-1 | °C | 960 |
Shock resistance(2) | Contactor open | | 10gn | 8gn | 8gn | 8gn | 6gn |
1/2 sine wave=11ms | Contactor closed | | 15gn | 15gn | 10gn | 10gn | 15gn |
Vibration resistance(2) | Contactor open | | 2gn | 2gn | 2gn | 2gn | 2gn |
5...300Hz | Contactor closed | | 4gn | 4gn | 4gn | 3gn | 4gn |
(1) Protection ensured for the connection cross-sections shown on the next page and for connection via cable.
(2) In the least favourable direction,without change of contact(coil supplied at Ue)